ZEPHYR GUIDE SPECIFICATIONS
Project Name Project No. Date
Project Location 11 40 00-2 Air Doors
Specifier Note: Delete options in the first paragraph below that are not included in this
section. Retain only those options in the first paragraph below that are required for a specific
project. Delete all options in the first paragraph below if heated air doors are not required.
A. Air doors[, electric heated] [, hot water heated] [, steam heated].
B. [Insert item description.]
1.3 RELATED REQUIREMENTS
Specifier Note: In this article, specify work specified in other sections that is related to work
of this section.
A. Section 04 22 00 - Concrete Unit Masonry: Blocking or reinforcing in wall as required
for attachment of air door.
B. Section 05 40 00 - Cold-Formed Metal Framing: Reinforcing in wall as required for
attachment of air door.
C. Section 06 10 00 - Rough Carpentry: Blocking in wall as required for attachment of air
door.
Specifier Note: If switches for air doors are mounted on door frames, retain either
Section 08 11 00 or 08 41 00 below to facilitate coordination.
D. Section 08 11 00 - Metal Doors and Frames: Coordinate installation of switches.
Specifier Note: Strip doors can be used in conjunction with air doors to provide an even
higher level of separation. Retain first paragraph below if required for a specific project.
Consult Berner catalog for a complete list of available strip doors.
E. Section 08 38 13 - Flexible Strip Doors: Coordinate installation of strip doors with
installation of air doors.
F. Section 08 41 00 - Entrances and Storefronts: Coordinate installation of switches.
Specifier Note: Retain the following paragraph if door openers or automatic door opening
assemblies are used. Air door must be positioned so air stream is not obstructed when
deflected 20 degrees to either side of centerline. If air stream strikes any obstruction (top
edge of the doorway, door opening device, etc.) effectiveness of unit will be reduced.
G. Section 08 71 00 - Door Hardware: Coordinate with installation of hardware.
Specifier Note: Retain any of the three following paragraphs if air doors are mounted above
ceiling. Delete if no units installed above ceiling.
H. Section 09 22 16 - Non-Structural Metal Framing: Framing and blocking above ceiling
as required for installation of air door.
I. Section 09 29 00 - Gypsum Board: Ceiling finish abutting air door.